Maximum trip time limits for different RCD types
Inspection Testing · Lesson 23 · Advanced
Purpose
Apply trip-time limits by device delay class and current field method, not by a generic ‘different RCD type’ table.
Learning objectives
- Use the current required method
- Separate field verification from type testing
- Prove polarity through the complete path
- Compare fault current with every affected rating
AC, A, F and B describe residual-current waveform capability; general versus S-type describes intentional delay. Field timing limits therefore cannot be selected from waveform type name alone.
Core theory
At the current rated-current AC compliance test, general non-delay devices are expected to operate within the applicable maximum (commonly 300 ms under current guidance).
S-type devices use a permitted operating window (commonly 130–500 ms at the stated rated-current test), because too-fast operation can defeat selectivity as well as too-slow operation failing protection.
Confirm product standard, application and edition. An S type is not suitable for 30 mA additional protection; RCD selection must also address DC components, frequency, voltage dependence, poles and upstream/downstream coordination.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| Non-delay | RCD without intentional selective time delay | Not applicable | Not applicable |
| Selective | Coordinated delay intended to let downstream protection operate first | Not applicable | Not applicable |
| Waveform type | Residual-current forms the RCD is designed to detect | Not applicable | Not applicable |
Assumptions: Supplied readings and criteria are fictional evidence; Current edition and exact equipment data remain governing.
- Minimum: 72 ms is below 130 ms.
- Meaning: It is too fast for the supplied selective window, even though it disconnected quickly.
- Action: Verify setting/device/test and resolve selectivity evidence.
It fails the supplied S-type timing window because minimum delay is also required.
Reasonableness check: The decision distinguishes the measured quantity, protective function and equipment rating instead of treating one tester result as a complete certificate.
- Applying obsolete half-rated/5× rules as universal requirements
- Selecting an RCD type from trip time alone
- Checking PFC only against the final-circuit breaker
Where this appears in practice
RCD, polarity and PFC verification confirms correct conductor/device operation and that installed equipment can safely interrupt credible faults.
Knowledge check
Is the fastest RCD trip always the best result?
No. Selective devices must also satisfy a minimum delay for coordination.
Answer: No. Selective devices must also satisfy a minimum delay for coordination.
Practical exercise
Classify results for general and S-type devices without confusing waveform type with time delay.
Summary
- Current field RCD testing is intentionally simplified
- Polarity requires both topology and final confirmation
- PFC is a worst-case rating and coordination check
Sources and review
- Changes to RCD testing in BS 7671:2018+A2:2022: IET Wiring Matters; 2022; confirm A4:2026/GN3 status; United Kingdom
- BS 7671 and Guidance Note 3: Inspection & Testing: IET; BS 7671:2018+A4:2026 / GN3 10th edition; transition rules apply; United Kingdom
- Minimizing unnecessary live testing for initial verification: IET Wiring Matters; 2025; United Kingdom
- GS38: Electrical test equipment for low-voltage systems: HSE; Fourth edition; Great Britain
Editorial review date: 2026-08-22. Professional electrical review is pending.