Correcting excessive Zs readings
Inspection Testing · Lesson 19 · Advanced
Purpose
Correct excessive loop impedance by locating the cause and re-verifying the complete protective design.
Learning objectives
- Select a safe valid method
- Protect connected equipment
- Interpret measured versus design values
- Diagnose without bypassing protective evidence
High Zs can arise from wrong supply data, long/undersized conductors, loose/corroded joints, damaged CPC, unsuitable protective device, high electrode impedance or measurement error. The remedy must address the cause.
Core theory
Repeat instrument/supply checks and compare Ze, R1+R2, calculated and measured Zs to locate whether the excess is external or within the circuit.
Inspect and test terminations/conductors; repair defects. Design options can include larger/parallel protective conductors, route changes, suitable protective device or RCD-based measure where permitted and fully coordinated.
Never use water/gas services as a designed fault path, increase a breaker rating to obtain a table value, or accept parallel-path Zs over failed continuity. Repeat all affected tests after change.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| ADS | Automatic disconnection of supply | Not applicable | Not applicable |
| Fault path | Complete conductive loop carrying earth-fault current | Not applicable | Not applicable |
| Corrective action | Repair/redesign addressing verified cause | Not applicable | Not applicable |
Assumptions: Supplied values and device limits are fictional design evidence; Instrument uncertainty and current edition data remain to be checked.
- Locate: Most impedance is internal: R1+R2 is 1.05 Ω.
- Inspect/design: Check route, length, CPC size and joints; repair or redesign the circuit/protection.
- Reverify: Repeat continuity, polarity, IR and loop/protection checks affected by work.
The internal circuit path dominates; investigate and correct it rather than blaming external Ze.
Reasonableness check: The conclusion retains units, test boundary and protective-device context; one favorable reading cannot excuse an unsafe method.
- Testing connected electronics at an unsuitable DC voltage
- Treating parallel paths as the designed CPC
- Comparing a measured Zs with the wrong device curve or an unqualified tabulated value
Where this appears in practice
IR and loop verification provide complementary evidence: insulation limits unintended current paths while loop impedance supports automatic disconnection under faults.
Knowledge check
Is increasing protective-device rating a valid default fix for excessive Zs?
No. It can worsen cable/protection coordination and must follow complete redesign.
Answer: No. It can worsen cable/protection coordination and must follow complete redesign.
Practical exercise
Diagnose four high-Zs cases using split Ze/R1+R2/measured data and propose defensible corrective actions.
Summary
- Choose voltage and connections from actual equipment
- Loop boundaries must be explicit
- Compare results with exact current design evidence
Sources and review
- BS 7671 and Guidance Note 3: Inspection & Testing: IET; BS 7671:2018+A4:2026 / GN3 10th edition; transition rules apply; United Kingdom
- Guidance Note 3 errata and diverted-neutral safety note: IET; GN3 9th-edition errata; use current GN3 procedure; United Kingdom
- GS38: Electrical test equipment for low-voltage systems: HSE; Fourth edition; Great Britain
Editorial review date: 2026-08-22. Professional electrical review is pending.