Disconnection time requirements: Table 41.1
Protection Fault Analysis · Lesson 9 · Intermediate
Purpose
Determine the required disconnection time from the earthing system, circuit type, voltage, and protective measure before selecting a Zs limit.
Learning objectives
- Use Table 41.1 context
- Distinguish final and distribution circuits
- Relate time to device current
- Avoid memorising 0.4 s as universal
Disconnection-time requirements limit how long dangerous touch voltage may persist. The applicable time is a classification result, not a universal domestic constant.
Core theory
Identify TN or TT arrangement, nominal line-to-earth voltage, final/distribution circuit, socket/current limits and other conditions, then use the current Table 41.1 and related regulations.
Once the required time is known, determine the current Ia that makes the exact device operate within that time and derive/check the permitted loop impedance using the current voltage factor or table/manufacturer data.
RCD fault protection uses its own operating characteristics and RA/Zs provisions; overcurrent protection, additional protection, continuity, bonding, and special-location rules remain coordinated.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| Disconnection time | Maximum permitted duration before ADS removes the fault | Not applicable | Not applicable |
| Ia | Current causing operation within the specified time | Not applicable | A |
| U0 | Nominal AC voltage to Earth | Not applicable | V |
Zs × Ia ≤ U0 × applicable minimum-voltage factorApply the equation and factors from the exact current edition; tables may already embody stated assumptions.
Ω × A ≤ VAssumptions: No circuit details supplied.
- System: Establish TN/TT and U0.
- Circuit: Classify final versus distribution and the applicable rating/use conditions.
- Rules: Check current Table 41.1, related exceptions, protective measure, and device data.
No time can be assigned until the system and circuit are classified under the current rules.
Reasonableness check: Different exposure and circuit contexts have different permitted durations.
- Applying 0.4 s universally
- Reading a table without its notes
- Using an instantaneous multiplier where a time curve is required
Where this appears in practice
Time classification precedes Zs limits, maximum length, and protection verification.
Knowledge check
What comes before choosing a maximum Zs from a table?
Classifying the system, circuit, required time, and exact protective device. The table value only applies within its stated scope.
Answer: Classifying the system, circuit, required time, and exact protective device. The table value only applies within its stated scope.
Practical exercise
For four fictional circuit descriptions, identify missing classification data before looking up any disconnection time.
Summary
- Required time is context-dependent
- Time determines device operating current
- Read table scope and notes
Sources and review
- Determining maximum earth fault loop impedance: IET Wiring Matters; 2023 technical article; United Kingdom
- How to verify automatic disconnection of supply for RCD-protected circuits: IET Wiring Matters; Issue 105, May 2025; United Kingdom
- Electricity at Work Regulations 1989: Guidance on Regulations: HSE; HSR25; Great Britain
- Inspection and Testing FAQs: IET; Current online guidance; United Kingdom
Editorial review date: 2026-08-21. Professional electrical review is pending.