PFC: what it is and why it matters
Protection Fault Analysis · Lesson 16 · Intermediate
Purpose
Define prospective fault current as the greatest credible current at a point for the fault types and supply configuration assessed.
Learning objectives
- Distinguish PEFC and PSCC
- Explain why PFC varies by location
- Relate PFC to device capability
- Include multiple-source scenarios
Prospective fault current is the current expected if a negligible-impedance fault occurs at the point considered. Both line-earth and live-conductor short-circuit paths may need assessment.
Core theory
Prospective earth fault current follows the earth-fault loop; prospective short-circuit current follows the live-conductor loop. The recorded PFC basis must cover the greater applicable result.
Source impedance, transformer/network strength, conductor impedance, parallel supplies, motors, generators, PV/storage converters, and operating configuration affect magnitude and X/R characteristics.
PFC establishes required device and assembly breaking/short-circuit withstand, conditional backup arrangements, conductor thermal stress, arc energy context, and test safety.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| PEFC | Prospective earth fault current | Not applicable | A or kA |
| PSCC | Prospective short-circuit current | Not applicable | A or kA |
| PFC | Prospective fault current basis recorded at a point | Not applicable | A or kA |
Screening only: If ≈ U / ZloopUse the correct fault voltage, loop, source contributions, impedance angle, and current-edition method.
AAssumptions: Both results valid for the same configuration.
- Compare: 4.1 kA exceeds 2.8 kA.
- Record: Use 4.1 kA as the greater prospective current basis.
- Verify: Check all device/assembly ratings and source configurations.
Use 4.1 kA as the greater PFC result for this screening context.
Reasonableness check: Capability must cover the more severe credible fault current.
- Recording only earth-fault current
- Ignoring alternate sources
- Calling the breaker rating the measured PFC
Where this appears in practice
PFC is required at origins and relevant distribution points for switchgear and protective-device selection.
Knowledge check
Why compare PEFC and PSCC?
The equipment must withstand or interrupt the greater applicable prospective current. Their loop impedances can differ.
Answer: The equipment must withstand or interrupt the greater applicable prospective current. Their loop impedances can differ.
Practical exercise
For three source configurations, list every contribution and the point at which PEFC/PSCC must be established.
Summary
- PFC depends on fault type and point
- Use the greater applicable value
- All credible sources matter
Sources and review
- Minimizing unnecessary live testing for initial verification: IET Wiring Matters; Issue 105, May 2025; United Kingdom
- Best Practice Guide 7: Test instrument accuracy and consistency: Electrical Safety First; Issue 2.1; United Kingdom
- BS 7671:2018+A4:2026 model EICR schedule: IET; Amendment 4:2026; United Kingdom
Editorial review date: 2026-08-21. Professional electrical review is pending.