Skip to main content
ElectraCore
LearnCalculatorsCircuit DesignerReferences
Saved
Educational use: ElectraCore supports learning and preliminary checks. It does not replace a competent electrician or engineer. Verify results, equipment data, and current local regulations before installation or live work.
Courses/Protection & Fault Analysis/Discrimination & Coordination

lesson · 7min · Lesson 23 of 29

Time discrimination

Course syllabusCourse overview
01Overcurrent Protection Devices
  1. ReadRewirable fuses vs cartridge fuses
  2. ReadMCB operating characteristics: B, C, D curves
  3. ReadRCBO: combined RCD + MCB operation
  4. ReadAFDD: arc fault detection
  5. quizDevice selection quiz
02Fault Loop Impedance
  1. ReadWhat is earth fault loop impedance?
  2. ReadZe: external impedance measurement
  3. ReadZs: total loop impedance calculations
  4. ReadDisconnection time requirements: Table 41.1
  5. exerciseZs calculation exercises
03RCDs and Residual Current
  1. ReadHow RCDs work: the core balance principle
  2. ReadRCD types: Type AC, A, F, B
  3. ReadRCD ratings: 10, 30, 100, 300mA
  4. ReadRCD testing and nuisance trips
  5. quizRCD selection quiz
04Prospective Fault Current
  1. ReadPFC: what it is and why it matters
  2. ReadCalculating PFC at the origin
  3. ReadPFC at distribution boards downstream
  4. ReadFault current rating of devices
  5. exercisePFC worked problems
05Discrimination & Coordination
  1. ReadWhat is discrimination and why it matters
  2. ReadCurrent discrimination
  3. ReadTime discrimination
  4. ReadEnergy discrimination for MCBs
  5. exerciseDiscrimination case study
06Testing for Protection
  1. ReadTesting Zs with loop testers
  2. ReadMeasuring PFC at the board
  3. ReadRCD trip time testing
  4. quizFinal assessment
Lesson · 7min
Lesson contents 0%

In this lesson

PurposeCore theoryWorked exampleKnowledge checkSources

In this lesson

PurposeCore theoryWorked exampleKnowledge checkSources
0% read
ElectraCore lesson handout

Time discrimination

Protection Fault Analysis · Lesson 23 · Advanced

AdvancedReview: professional review pending

Purpose

Coordinate intentional time delays while retaining required disconnection and equipment-withstand performance.

Before you beginCurrent discrimination · Disconnection time

Learning objectives

  • Explain grading margin
  • Coordinate adjustable delays
  • Check maximum disconnection time
  • Account for fault energy

Time discrimination delays the upstream device long enough for a downstream device to clear. The delay must include device tolerances and breaker clearing time while remaining safe for conductors, equipment, and shock protection.

SELECTIVITY AND COORDINATIONSELECTIVITY AND COORDINATIONSOURCETRIPfault / loadcurves / time / I-squared-t / paired data

Core theory

A grading margin is not merely the difference between dial settings; it includes downstream clearing time, upstream tolerance, relay error, breaker travel, overshoot, and the manufacturer's coordination method.

Definite-time and inverse-time functions can be graded, but instantaneous or high-set elements may still overlap and defeat selectivity at high fault current.

Every delay is checked against automatic-disconnection requirements, adiabatic/thermal withstand, arc-energy exposure, source stability, and the maximum fault-clearing duty of the assembly.

Terms, symbols, and units
TermMeaningSymbolUnit
Grading marginTime separation allowing the downstream device to clear before upstream operationNot applicableNot applicable
Definite timeOperation after an approximately fixed intentional delay above pickupNot applicableNot applicable
Inverse timeOperating time decreases as current increasesNot applicableNot applicable
Worked exampleA downstream breaker can clear in 0.18 s at a stated fault current and the coordination study requires 0.12 s margin. What is the earliest candidate upstream clearing time?

Assumptions: Times use compatible manufacturer definitions; Other tolerances are already included in the 0.12 s margin.

  1. Downstream: Use the maximum clearing time: 0.18 s.
  2. Margin: Add 0.12 s rather than subtracting it.
  3. Candidate: 0.18 s + 0.12 s = 0.30 s, then check all safety limits.

The earliest candidate upstream clearing time is 0.30 s; it is not approved until the remaining checks pass.

Reasonableness check: The upstream device must remain closed through downstream clearing plus the grading allowance.

Common mistakes
  • Comparing relay pickup times instead of total clearing
  • Ignoring instantaneous elements
  • Adding delay without a withstand check

Where this appears in practice

Time grading is common in multi-level distribution, industrial switchboards, and selective residual-current protection.

SafetyIntentional delay increases fault duration and incident energy. Settings require authorised protection engineering and controlled commissioning.
Local code checkConfirm the current BS 7671 edition, exact device and assembly data, manufacturer selectivity/backup tables, required disconnection times, test-instrument ratings, safe system of work, and certificate schedule. A generic rating ratio or one field reading is not proof of coordination or compliance.

Knowledge check

Does a longer upstream delay always improve the design?

No. It may breach disconnection, withstand, or arc-energy constraints.

Answer: No. It may breach disconnection, withstand, or arc-energy constraints.

Practical exercise

Create a paper time-grading sequence and list every constraint that could reject it.

Summary

  • Margins include tolerances and clearing
  • High-set elements also need coordination
  • Delay must remain within safety limits

Sources and review

  • Guidance Note 6: Protection Against Overcurrent: IET; 10th edition, BS 7671:2018+A4:2026; United Kingdom
  • Inspection and Testing FAQs: IET; Current online guidance; United Kingdom
  • Electricity at Work Regulations 1989: HSR25: Health and Safety Executive; Third edition; Great Britain

Editorial review date: 2026-08-21. Professional electrical review is pending.

Educational material for learning and preliminary checks. Verify current local requirements and exact equipment instructions. This lesson does not replace competent professional work.

Personal study record

Lesson notes

Ready

Notes are stored on this device unless you export them.