MAKE IT STICK
A little practice. A stronger idea.
What is earth fault loop impedance?
Protection Fault Analysis · Lesson 6 · Intermediate
Purpose
Model the complete earth-fault loop and connect its impedance to fault current, touch voltage, and automatic disconnection.
Learning objectives
- Trace a TN fault loop
- Define Ze and R1+R2
- Relate Zs to fault current
- Recognise TT/RCD differences
Earth fault loop impedance is the opposition around the complete fault-current path from source line through the fault and protective return to the source.
Build an equivalent fault loop
Follow the three steps, then explain the relationship in your own words.
The source voltage and external path belong to the equivalent loop model.
Enlarge for small labels. Focus the drawing to scroll with arrow keys.
Text equivalent: all three steps
- Source and external path. The source voltage and external path belong to the equivalent loop model.
- Add conductor paths. Internal outgoing and protective return paths add to the supplied loop impedance.
- Relate loop impedance to current. Prospective current uses the complete loop. A current estimate alone does not establish protective-device operating time.
Model boundary: Equivalent loop only; actual earthing arrangements and protection coordination require separate review.
FROM THE OBJECT TO THE IDEA
The fault-current lens
See why a smaller loop impedance means a larger fault current. Compare an original equipment illustration with the model diagram, then change the controls to see the relationship.
Generic teaching equipment · dimensions and ratings are not specifications.Core theory
For a TN circuit, the loop includes source impedance, line conductors to the fault, protective conductors back to the source, connections, and the fault itself; parallel metallic paths can influence a measurement.
A lower loop impedance generally permits greater fault current, helping an overcurrent device disconnect faster, but the exact time comes from its curve and the applicable minimum-voltage/temperature basis.
In TT systems the electrode path often cannot operate an overcurrent device within the required time, so RCD fault protection and the applicable RA relationship are central; a high result may still reveal a defect.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| Zs | Earth fault loop impedance of a circuit | Not applicable | Ω |
| Ze | External earth fault loop impedance | Not applicable | Ω |
| R1+R2 | Circuit line plus protective-conductor resistance | Not applicable | Ω |
Conceptually: Zs ≈ Ze + (R1 + R2); fault current ≈ U / ZsUse the current standard's voltage factors, temperature basis, device data, and measured or calculated method, not this conceptual screening equation alone.
Ω and AAssumptions: Purely resistive screening; Nominal voltage only.
- Equation: I=U/Z.
- Substitute: I=230/1.0.
- Screen: Idealised current is 230 A; now use the actual design basis and device curve.
230 A idealised screening current, not a compliance conclusion.
Reasonableness check: One ohm at 230 volts gives hundreds, not tens, of amperes.
- Treating Zs=Ze+R1+R2 as exact under all conditions
- Ignoring conductor temperature
- Calling low Zs proof of every protective measure
Where this appears in practice
Loop analysis supports ADS design, maximum circuit length, device selection, and diagnostic testing.
Knowledge check
Does a calculated fault current alone prove required disconnection?
No. Compare the applicable current/time with the exact protective-device characteristic and full requirements.
Answer: No. Compare the applicable current/time with the exact protective-device characteristic and full requirements.
Practical exercise
Draw TN-S, TN-C-S, and TT fault loops and mark which impedance components dominate each conceptual path.
Summary
- Zs covers the complete fault path
- Impedance influences fault current
- Device/time and earthing method decide compliance
Sources and review
- Determining maximum earth fault loop impedance: IET Wiring Matters; 2023 technical article; United Kingdom
- How to verify automatic disconnection of supply for RCD-protected circuits: IET Wiring Matters; Issue 105, May 2025; United Kingdom
- Electricity at Work Regulations 1989: Guidance on Regulations: HSE; HSR25; Great Britain
- Inspection and Testing FAQs: IET; Current online guidance; United Kingdom
Editorial review date: 2026-08-21. Professional electrical review is pending.