Calculating voltage drop for single-phase
Cable Sizing · Lesson 13 · Intermediate
Purpose
Calculate single-phase voltage drop and test it against an explicitly allocated design limit.
Learning objectives
- Calculate ΔV
- Convert to percent
- Compare with budget
- Revise a design
A single-phase calculation is only defensible when current, length and coefficient share the same route and design condition.
Core theory
Use design current appropriate to the load, not automatically the protective-device rating. Account for harmonic-rich or constant-power loads where the standard or equipment behavior requires it.
Compare the accumulated origin-to-load drop with the applicable current-edition recommendation and the equipment's declared voltage range. A pass against one does not prove the other.
If the result fails, options include larger conductors, shorter route, higher distribution voltage, load redistribution or local transformation. Follow this with every thermal and fault check again.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| Single-phase circuit | Circuit with line and return-current path | Not applicable | Not applicable |
| Route length | One-way installed length used by the selected table method | L | m |
| Terminal voltage | Voltage available at the load terminals | Not applicable | V |
Uload ≈ Uorigin − ΔVAn approximate steady-state relation; confirm source voltage and equipment behavior.
VAssumptions: Matching table coefficient; Steady design load.
- Drop: ΔV = 4.4×31×45/1000 = 6.138 V.
- Percent: 100×6.138/230 = 2.6687%.
- State: Report about 6.14 V and 2.67%, then compare with the allocated limit.
Illustrative drop is 6.14 V, or 2.67% on a 230 V basis.
Reasonableness check: The result is below the roughly 8.5 V example from a longer/higher-coefficient path.
- Using In when Ib is required
- Comparing only the final-circuit segment
- Rounding before the decision
Where this appears in practice
Single-phase feeders, socket circuits and heating loads require whole-path budgeting.
Knowledge check
What current belongs in the basic table calculation?
The applicable design current for the stated load case. Protective-device rating has a different design role.
Answer: The applicable design current for the stated load case. Protective-device rating has a different design role.
Practical exercise
Screen two supplied conductor coefficients, then rerun all affected design checks for the selected option.
Summary
- Keep inputs on one basis
- Assess volts and percent
- A redesign changes other checks
Sources and review
- BS 7671:2018+A4:2026 Requirements for Electrical Installations: IET/BSI; Current edition and corrigenda must be confirmed; United Kingdom
- Earthing and Bonding FAQs: SWA armour as CPC: IET; Current online guidance; United Kingdom
- Avoiding danger from underground services (HSG47): Health and Safety Executive; Third edition; Great Britain
Editorial review date: 2026-08-22. Professional electrical review is pending.