How CCC tables work: Appendix 4
Cable Sizing · Lesson 1 · Intermediate
Purpose
Use current-carrying-capacity tables as one thermal stage in a complete cable design.
Learning objectives
- Distinguish Ib, In, It and Iz
- Select the applicable table
- Apply factors on the correct basis
- Identify remaining design checks
A table value is conditional: it belongs to a stated cable, number of loaded conductors, reference method and reference environment. It is not a free-standing amp rating.
Core theory
The usual coordination is Ib ≤ In ≤ Iz: load design current does not exceed device rating, and device rating does not exceed the cable's corrected current-carrying capacity. Overload-protection rules can change the precise design expression, so use the current clause.
It is the tabulated capacity at the table's reference conditions. Iz is the capacity for the actual declared conditions after only the applicable corrections are used on the basis required by that table.
Choose cable type, insulation temperature, conductor material, loaded conductors and physical installation before reading a row. Then separately verify voltage drop, fault protection/disconnection, short-circuit withstand, terminals, harmonics, neutral, mechanical/environmental suitability and regulations.
| Term | Meaning | Symbol | Unit |
|---|---|---|---|
| Design current | Expected circuit current used for design | Ib | A |
| Device rating | Rated or setting current of the protective device | In | A |
| Tabulated capacity | Capacity at the table's stated reference conditions | It | A |
| Corrected capacity | Capacity for the declared installed conditions | Iz | A |
Ib ≤ In ≤ IzBasic coordination only; apply the exact current standard's overload and correction-factor procedure.
ampere (A)Assumptions: The table and factors are explicitly supplied; No other correction applies.
- Product: Ca × Cg = 0.94 × 0.80 = 0.752.
- Correct: Iz = 37 × 0.752 = 27.824 A.
- Decision: This would not support a 32 A device under the basic relation.
Illustrative Iz is 27.8 A; select/recalculate rather than rounding it into compliance.
Reasonableness check: Both factors are below one, so Iz must be lower than It.
- Treating a memorised size as universally rated
- Mixing table families or conductor counts
- Applying factors twice
- Stopping after the thermal check
Where this appears in practice
Design schedules and verification records should preserve every table, column, factor, assumption and result.
Knowledge check
Why can two identical cable sizes have different capacities?
Heat escape and reference conditions can differ. Construction, loading, environment and installation geometry all matter.
Answer: Heat escape and reference conditions can differ. Construction, loading, environment and installation geometry all matter.
Practical exercise
Build a traceable selection record from a supplied table extract; do not use remembered values.
Summary
- A table value is conditional
- Ib, In, It and Iz are different
- Thermal capacity is only one design gate
Sources and review
- BS 7671:2018+A4:2026 Requirements for Electrical Installations: IET/BSI; Current edition and corrigenda must be confirmed; United Kingdom
- Guidance Note 6: Protection Against Overcurrent: IET; Current edition must be confirmed; United Kingdom
- Electricity at Work Regulations 1989: HSR25: Health and Safety Executive; Current online edition; Great Britain
Editorial review date: 2026-08-22. Professional electrical review is pending.