GuidesSafety
Intermediate8 min readUpdated 2024

RCD Types — AC, A, F and B Explained

Which residual current device to fit, why it matters for EV chargers, solar and VSDs, and what the ratings mean.

BS 7671:2018+A2:2022BS EN 61008 / 61009BS EN 62423
An RCD measures the current going out against the current coming back. If they don't match, current is leaking to earth — possibly through a person — and the device trips. The catch is that modern electronics distort the residual current, and the cheapest RCD (Type AC) can be 'blinded' by it. Choosing the right type is a safety decision, not a cost one.

How an RCD works

RCD · CORE-BALANCE PRINCIPLETOROIDAL COREL → IN ← ITRIP COILHealthy:I(L) = I(N)flux cancels → no tripFault:I(L) − I(N) = ΔIΔI ≥ I∆n → trips <300 ms

Line and neutral both pass through a toroidal core. In a healthy circuit the two currents are equal and opposite, so their magnetic fields cancel. Any imbalance — current returning via the earth path instead of the neutral — leaves a net flux that induces a current in a sense winding and releases the trip mechanism.

ΔI = | I(line) − I(neutral) |
When ΔI reaches the rated residual current IΔn, the device operates.

Ratings: what 30 mA actually buys you

10 mASpecial locations, medical, high-risk fixed equipment
30 mAAdditional protection against electric shock — socket outlets, most final circuits
100 mAFire protection / larger sub-mains where 30 mA nuisance-trips
300–500 mAFire protection on distribution circuits; not shock protection

Only a 30 mA (or lower) device provides 'additional protection' against electric shock. BS 7671 requires it for socket outlets rated up to 32 A intended for general use, and for circuits in bathrooms and similar.

Test currentMaximum disconnection time (30 mA RCD)
IΔn (30 mA)300 ms
2 × IΔn (60 mA)150 ms
5 × IΔn (150 mA)40 ms
General-type RCD to BS EN 61008/61009. 'S' (time-delayed) types allow longer times for selectivity.

Choosing the type by waveform

RCD TYPES · RESIDUAL WAVEFORM DETECTEDType ACsine onlydetected by: AC A F BType A / F+ pulsating d.c.detected by: A F BType B+ smooth d.c.detected by: B only
TypeDetectsTypical use
ACSinusoidal a.c. residual onlyLegacy resistive loads. No longer the default choice.
Aa.c. + pulsating d.c. residualModern general use — anything with electronics/SMPS. The new baseline.
Fa.c. + pulsating d.c. + mixed frequenciesSingle-phase inverter loads, some washing machines, class-1 VSD equipment.
BAll of the above + smooth d.c. residualThree-phase EV chargers, PV inverters without isolation, three-phase VSDs.
Type AC is being designed out
Amendment 2 to BS 7671 effectively pushes Type A as the minimum for most circuits, because switched-mode power supplies (chargers, LED drivers, TVs) produce pulsating d.c. that can stop a Type AC device from tripping. Fit Type A unless a higher type is required.
EV charging is the common decision point
An EV charge point needs at least 30 mA Type A plus d.c. residual detection ≥ 6 mA — provided either by a Type B RCD or by a Type A RCD combined with built-in 6 mA d.c. protection (RDC-DD) in the charger. Check the charger's data sheet before choosing the RCD.

RCD, RCBO or main-switch RCD?

A stand-alone RCD only does earth-fault protection; it must be paired with overcurrent protection. An RCBO combines a 30 mA RCD and an MCB in one module, so a fault on one circuit trips only that circuit — far better than a shared RCD taking out half the board. For new work, per-circuit RCBOs are usually the right answer for both safety and nuisance-trip resilience.

Reference material for qualified electrical work. Figures follow BS 7671 and the IET On-Site Guide unless stated; always confirm against the current edition and the standard that applies to your installation.